Search Results (403 CVEs found)

CVE Vendors Products Updated CVSS v3.1
CVE-2022-47374 1 Siemens 18 6ag1414-3em07-7ab0, 6ag1414-3em07-7ab0 Firmware, 6ag1416-3es07-7ab0 and 15 more 2026-02-25 7.5 High
A vulnerability has been identified in SIMATIC PC-Station Plus (All versions), SIMATIC S7-400 CPU 412-2 PN V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions), SINAMICS S120 (incl. SIPLUS variants) (All versions < V5.2 SP3 HF15), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions). The affected products do not handle HTTP(S) requests to the web server correctly. This could allow an attacker to exhaust system resources and create a denial of service condition for the device.
CVE-2023-46156 1 Siemens 145 Simatic Drive Controller Cpu 1504d Tf, Simatic Drive Controller Cpu 1504d Tf Firmware, Simatic Drive Controller Cpu 1507d Tf and 142 more 2026-02-25 7.5 High
Affected devices improperly handle specially crafted packets sent to port 102/tcp. This could allow an attacker to create a denial of service condition. A restart is needed to restore normal operations.
CVE-2023-46284 1 Siemens 4 Opcenter Quality, Simatic Pcs Neo, Sinumerik Integrate Runmyhmi \/automotive and 1 more 2026-02-25 7.5 High
A vulnerability has been identified in Opcenter Execution Foundation (All versions < V2407), Opcenter Quality (All versions < V2312), SIMATIC PCS neo (All versions < V4.1), SINEC NMS (All versions < V2.0 SP1), Totally Integrated Automation Portal (TIA Portal) V14 (All versions), Totally Integrated Automation Portal (TIA Portal) V15.1 (All versions), Totally Integrated Automation Portal (TIA Portal) V16 (All versions), Totally Integrated Automation Portal (TIA Portal) V17 (All versions < V17 Update 8), Totally Integrated Automation Portal (TIA Portal) V18 (All versions < V18 Update 3). The affected application contains an out of bounds write past the end of an allocated buffer when handling specific requests on port 4002/tcp and 4004/tcp. This could allow an attacker to crash the application. The corresponding service is auto-restarted after the crash.
CVE-2023-29131 1 Siemens 1 Simatic Cn 4100 Firmware 2026-02-18 7.4 High
A vulnerability has been identified in SIMATIC CN 4100 (All versions < V2.5). Affected device consists of an incorrect default value in the SSH configuration. This could allow an attacker to bypass network isolation.
CVE-2023-29130 1 Siemens 1 Simatic Cn 4100 Firmware 2026-02-18 9.9 Critical
A vulnerability has been identified in SIMATIC CN 4100 (All versions < V2.5). Affected device consists of improper access controls in the configuration files that leads to privilege escalation. An attacker could gain admin access with this vulnerability leading to complete device control.
CVE-2025-40944 1 Siemens 15 Simatic Et 200al Im 157-1 Pn, Simatic Et 200mp Im 155-5 Pn Hf, Simatic Et 200sp Im 155-6 Mf Hf and 12 more 2026-01-14 7.5 High
A vulnerability has been identified in SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0) (All versions), SIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0) (All versions >= V4.2.0), SIMATIC ET 200SP IM 155-6 MF HF (6ES7155-6MU00-0CN0) (All versions), SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants) (All versions < V1.3), SIMATIC ET 200SP IM 155-6 PN R1 (6ES7155-6AU00-0HM0) (All versions < V6.0.1), SIMATIC ET 200SP IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0) (All versions >= V4.2.0), SIMATIC ET 200SP IM 155-6 PN/3 HF (6ES7155-6AU30-0CN0) (All versions < V4.2.2), SIMATIC PN/MF Coupler (6ES7158-3MU10-0XA0) (All versions), SIMATIC PN/PN Coupler (6ES7158-3AD10-0XA0) (All versions < V6.0.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0) (All versions >= V4.2.0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-2CN0) (All versions >= V4.2.0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-7CN0) (All versions >= V4.2.0), SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU01-1CN0) (All versions >= V4.2.0), SIPLUS ET 200SP IM 155-6 PN HF TX RAIL (6AG2155-6AU01-4CN0) (All versions >= V4.2.0), SIPLUS NET PN/PN Coupler (6AG2158-3AD10-4XA0) (All versions < V6.0.0). Affected devices do not properly handle S7 protocol session disconnect requests. When receiving a valid S7 protocol Disconnect Request (COTP DR TPDU) on TCP port 102, the devices enter an improper session state. This could allow an attacker to cause the device to become unresponsive, leading to a denial-of-service condition that requires a power cycle to restore normal operation.
CVE-2025-40805 1 Siemens 24 Industrial Edge Cloud Device (iecd), Industrial Edge Device Kit, Industrial Edge Own Device (ieod) and 21 more 2026-01-14 10 Critical
Affected devices do not properly enforce user authentication on specific API endpoints. This could facilitate an unauthenticated remote attacker to circumvent authentication and impersonate a legitimate user. Successful exploitation requires that the attacker has learned the identity of a legitimate user.
CVE-2022-22965 6 Cisco, Oracle, Redhat and 3 more 45 Cx Cloud Agent, Commerce Platform, Communications Cloud Native Core Automated Test Suite and 42 more 2025-10-30 9.8 Critical
A Spring MVC or Spring WebFlux application running on JDK 9+ may be vulnerable to remote code execution (RCE) via data binding. The specific exploit requires the application to run on Tomcat as a WAR deployment. If the application is deployed as a Spring Boot executable jar, i.e. the default, it is not vulnerable to the exploit. However, the nature of the vulnerability is more general, and there may be other ways to exploit it.
CVE-2014-0160 13 Broadcom, Canonical, Debian and 10 more 37 Symantec Messaging Gateway, Ubuntu Linux, Debian Linux and 34 more 2025-10-22 7.5 High
The (1) TLS and (2) DTLS implementations in OpenSSL 1.0.1 before 1.0.1g do not properly handle Heartbeat Extension packets, which allows remote attackers to obtain sensitive information from process memory via crafted packets that trigger a buffer over-read, as demonstrated by reading private keys, related to d1_both.c and t1_lib.c, aka the Heartbleed bug.
CVE-2017-5689 3 Hpe, Intel, Siemens 71 Proliant Ml10 Gen9 Server, Proliant Ml10 Gen9 Server Firmware, Active Management Technology Firmware and 68 more 2025-10-22 9.8 Critical
An unprivileged network attacker could gain system privileges to provisioned Intel manageability SKUs: Intel Active Management Technology (AMT) and Intel Standard Manageability (ISM). An unprivileged local attacker could provision manageability features gaining unprivileged network or local system privileges on Intel manageability SKUs: Intel Active Management Technology (AMT), Intel Standard Manageability (ISM), and Intel Small Business Technology (SBT).
CVE-2025-30176 1 Siemens 5 Simatic Pcs Neo, Sinec Nms, Sinema Remote Connect and 2 more 2025-10-03 7.5 High
A vulnerability has been identified in SIMATIC PCS neo V4.1 (All versions), SIMATIC PCS neo V5.0 (All versions), SINEC NMS (All versions < V4.0), SINEMA Remote Connect (All versions), Totally Integrated Automation Portal (TIA Portal) V17 (All versions), Totally Integrated Automation Portal (TIA Portal) V18 (All versions), Totally Integrated Automation Portal (TIA Portal) V19 (All versions), Totally Integrated Automation Portal (TIA Portal) V20 (All versions), User Management Component (UMC) (All versions < V2.15.1.1). Affected products contain a out of bound read buffer overflow vulnerability in the integrated UMC component. This could allow an unauthenticated remote attacker to cause a denial of service condition.
CVE-2025-30175 1 Siemens 5 Simatic Pcs Neo, Sinec Nms, Sinema Remote Connect and 2 more 2025-10-03 7.5 High
A vulnerability has been identified in SIMATIC PCS neo V4.1 (All versions), SIMATIC PCS neo V5.0 (All versions), SINEC NMS (All versions < V4.0), SINEMA Remote Connect (All versions), Totally Integrated Automation Portal (TIA Portal) V17 (All versions), Totally Integrated Automation Portal (TIA Portal) V18 (All versions), Totally Integrated Automation Portal (TIA Portal) V19 (All versions), Totally Integrated Automation Portal (TIA Portal) V20 (All versions), User Management Component (UMC) (All versions < V2.15.1.1). Affected products contain a out of bound write buffer overflow vulnerability in the integrated UMC component. This could allow an unauthenticated remote attacker to cause a denial of service condition.
CVE-2025-40798 1 Siemens 3 Simatic, Simatic Pcs Neo, User Management Component 2025-10-03 7.5 High
A vulnerability has been identified in SIMATIC PCS neo V4.1 (All versions), SIMATIC PCS neo V5.0 (All versions), User Management Component (UMC) (All versions < V2.15.1.3). Affected products contain a out-of-bounds read vulnerability in the integrated UMC component. This could allow an unauthenticated remote attacker to cause a denial of service condition.
CVE-2025-40797 1 Siemens 3 Simatic, Simatic Pcs Neo, User Management Component 2025-10-03 7.5 High
A vulnerability has been identified in SIMATIC PCS neo V4.1 (All versions), SIMATIC PCS neo V5.0 (All versions), User Management Component (UMC) (All versions < V2.15.1.3). Affected products contain a out-of-bounds read vulnerability in the integrated UMC component. This could allow an unauthenticated remote attacker to cause a denial of service condition.
CVE-2025-40796 1 Siemens 3 Simatic, Simatic Pcs Neo, User Management Component 2025-10-03 7.5 High
A vulnerability has been identified in SIMATIC PCS neo V4.1 (All versions), SIMATIC PCS neo V5.0 (All versions), User Management Component (UMC) (All versions < V2.15.1.3). Affected products contain a out-of-bounds read vulnerability in the integrated UMC component. This could allow an unauthenticated remote attacker to cause a denial of service condition.
CVE-2025-40795 1 Siemens 3 Simatic, Simatic Pcs Neo, User Management Component 2025-10-03 9.8 Critical
A vulnerability has been identified in SIMATIC PCS neo V4.1 (All versions), SIMATIC PCS neo V5.0 (All versions), User Management Component (UMC) (All versions < V2.15.1.3). Affected products contain a stack-based buffer overflow vulnerability in the integrated UMC component. This could allow an unauthenticated remote attacker to execute arbitrary code or to cause a denial of service condition.
CVE-2025-40804 1 Siemens 1 Simatic 2025-09-09 9.1 Critical
A vulnerability has been identified in SIMATIC Virtualization as a Service (SIVaaS) (All versions). The affected application exposes a network share without any authentication. This could allow an attacker to access or alter sensitive data without proper authorization.
CVE-2024-30321 1 Siemens 3 Simatic Pcs 7, Simatic Wincc, Simatic Wincc Runtime Professional 2025-08-27 5.9 Medium
A vulnerability has been identified in SIMATIC PCS 7 V9.1 (All versions < V9.1 SP2 UC05), SIMATIC WinCC Runtime Professional V18 (All versions < V18 Update 5), SIMATIC WinCC Runtime Professional V19 (All versions < V19 Update 2), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Update 23), SIMATIC WinCC V7.5 (All versions < V7.5 SP2 Update 17), SIMATIC WinCC V8.0 (All versions < V8.0 Update 5). The affected products do not properly handle certain requests to their web application, which may lead to the leak of privileged information. This could allow an unauthenticated remote attacker to retrieve information such as users and passwords.
CVE-2023-52891 1 Siemens 6 Simatic Energy Manager Basic, Simatic Energy Manager Pro, Simatic Ipc Diagbase and 3 more 2025-08-27 5.3 Medium
A vulnerability has been identified in SIMATIC Energy Manager Basic (All versions < V7.5), SIMATIC Energy Manager PRO (All versions < V7.5), SIMATIC IPC DiagBase (All versions), SIMATIC IPC DiagMonitor (All versions), SIMIT V10 (All versions), SIMIT V11 (All versions < V11.1). Unified Automation .NET based OPC UA Server SDK before 3.2.2 used in Siemens products are affected by a similar vulnerability as documented in CVE-2023-27321 for the OPC Foundation UA .NET Standard implementation. A successful attack may lead to high load situation and memory exhaustion, and may block the server.
CVE-2023-32737 1 Siemens 1 Simatic Step 7 2025-08-27 6.3 Medium
A vulnerability has been identified in SIMATIC STEP 7 Safety V18 (All versions < V18 Update 2). Affected applications do not properly restrict the .NET BinaryFormatter when deserializing user-controllable input. This could allow an attacker to cause a type confusion and execute arbitrary code within the affected application. This is the same issue that exists for .NET BinaryFormatter https://docs.microsoft.com/en-us/visualstudio/code-quality/ca2300.